DPM Gen2 Series UPS, 250-1750 kVA, 380/400/415 Vac
Technical Specifications
Model
DPM-250K / DPM-500K(1) / DPM-750K(1) / DPM-1000K
DPM-1250K / DPM-1500K(1) / DPM-1750K(1)
Power Rating
● DPM-250K
250 kVA / 250 kW
● DPM-500K
500 kVA / 500 kW
● DPM-750K
750 kVA / 750 kW
● DPM-1000K
1000 kVA / 1000 kW
● DPM-1250K
1250 kVA / 1250 kW
● DPM-1500K
1500 kVA / 1500 kW
● DPM-1750K
1750 kVA / 1750 kW
Parallel Configuration
Up to 8 units
Input
Nominal Voltage
380/ 400/ 415 Vac, 3P3W+PE or 3P4W+PE
Voltage Range
323-477 Vac (100% load)
Frequency Range
40-70 Hz
Total Harmonic Distortion (THDi)
< 3% (100% resistive load)
Power Factor
> 0.99 (100% load)
Short Circuit Withstand Rating
● DPM-250-750K
65 kA
● DPM-1000-1750K
100 kA
Connection
Single or dual feed
Output
Nominal Voltage
380/ 400/ 415 Vac, 3P3W+PE or 3P4W+PE
Voltage Regulation
±1% (static)
Frequency
50/60 ± 0.05 Hz
Total Harmonic Distortion (THDv)
< 1% (linear load)
Power Factor
1
Overload Capability
< 110%: continues, 110-125%: 10 mins, 126-150%: 1 min, > 150%: 1 sec
Current Crest Ratio
3:1
Efficiency
Online Mode
Up to 97.3%
Clean Mode (VI)
Up to 99%
Battery
Battery Type
VRLA, Vented lead-acid, Lithium-ion, Ni-Zinc
Nominal Voltage
480 Vdc
Quantity
34-35(2), 36-46 pcs (VRLA 12 V)
Charge Current
● DPM-250K
125 A
● DPM-500K
250 A
● DPM-750K
375 A
● DPM-1000K
500 A
● DPM-1250K
625 A
● DPM-1500K
750 A
● DPM-1750K
875 A
Protection Design
Battery shunt trip x1, Battery temperature detection x4, Battery breaker status dry contact x1
Communication Interface
Display
10-inch color touchscreen
Port
Smart slot x2, Modbus (RS-485) port x1, REPO port x1, Input dry contact x6, Output dry contact x6, Synchronized Multiple Bus (SMB) x2, Breaker status detection x4, EMS/Console port x1, Ethernet x1
Remote Emergency Power Off (REPO)
Option
Protocols
SNMP, Modbus RTU, Modbus TCP/IP, HTTP(S), SNTP, SMTP, BOOTP, DHCP
Physical
Dimensions (W x D x H)
● DPM-250K
1030 x 990 x 2000 mm
● DPM-1000K
3070 x 990 x 2000 mm
● DPM-1250K
3400 x 990 x 2000 mm
Net Weight
● DPM-250K
675.5 kg
● DPM-1000K
2450 kg
● DPM-1250K
2836.3 kg
Environment
Operating Temperature
0 to 40°C
Humidity
0-95% (non-condensing)
Altitude
0-2,000 m (derating 1%/100m from 1,001-2,000 m)
Conformance
Safety
IEC 62040-1, CE
EMC
IEC 62040-2
Performance
IEC 62040-3
Sustainability
RoHS, REACH, Energy Star
Features
Standard
⦁ Advance power walk-in for generator
⦁ Backfeed protection with contactor
⦁ Burn-in test without load bank
⦁ Cold start function
⦁ Synchronized multiple bus (SMB)
⦁ Frequency conversion
⦁ Battery shunt trip
⦁ Auxiliary power 48 Vdc for shunt trip
⦁ Failure prediction
Optional
⦁ Grid interactive
⦁ Software integration with Delta Lithium-ion battery BMS
⦁ DC battery ground fault detector
⦁ Integrated battery switch cabinet
⦁ IR scan window
(1) Upcoming product
(2) 34-35 pcs require service setting and load derating
(2) 34-35 pcs require service setting and load derating
All specifications are subject to change without prior notice
Produto disponível para as regiões a seguir:
|
Pedir Um Orçamento |