• Delta InfraSuite Cooling
  • Liquid-to-Air Coolant Distribution Unit (L2A CDU), 115 kW

    Technical Specifications

    Model
    L2A CDU-115
    Nominal Cooling Capacity
    115 kW
    Deployment
     
    Ambient Temperature
    35°C
    Airflow Rate
    13,908 CFM
    Coolant Supply Temperature
    45°C
    Coolant Flow Rate
    138 LPM
    Coolant Supply Pressure
    34 psi
    Approach Temperature
    10°C
    Coolant Feed Location
    Front
    Power Supply
     
    Nominal Power Supply Voltage
    380/400/415/480 Vac, 3P4W+PE
    Operating Voltage Rangel
    312-528 Vac
    Frequency
    50/60 Hz
    Maximum Power Consumption
    18 kW
    Dual Power Feed
    Standard
    Physical
     
    Dimensions (W x D x H)
    1200 x 1066 x 2286 mm
    Net Weight
    1200 kg
    Communication interface
     
    Display
    LCD touchscreen (optional)
    Protocols
    Modbus RTU
    Environment
     
    Operating Temperature
    10 to 35°C
    Humidity
    20-80%
    Conformance
     
    Safety
    UL
    Features
     
    Standard
     
    ▲ Leak Detection
     
    ▲ Networking Remote Monitoring/Control
     
    ▲ Individual Fan Fail Sensing
     
    ▲ Variable DC Fans
     
    All specifications are subject to change without prior notice.
     

    Producto disponible para las siguientes regiones:

    EMEA América Latina

      

    Solicite Una Cotización
    First Name *
    Last Name *
    Company *
    Job Title *
    Work Email *
    Phone *
    Estado / Provincia
    Country *
    Products you are interested in *
    Message *
    Suscribir Boletín *
     

    top