HPH Series UPS, Three Phase, 20/30/40/60 kVA/kW, 208/120V
Technical Specifications
Model
HPH-20K-LV-B / HPH-30K-LV-B / HPH-40K-LV-B / HPH-60K-LV-B
HPH-20K-LV-BN / HPH-30K-LV-BN / HPH-40K-LV-BN / HPH-60K-LV-BN
Power Rating
[20K]: 20kVA/20kW
[30K]: 30kVA/30kW
[40K]: 40kVA/40kW
[60K]: 60kVA/60kW
Input
Nominal Voltage
208/120Vac, 220/127Vac (3 phase, 4-wire + G)
Voltage Range
125~253Vac(L-L) / 72~146Vac(L-N)*
Frequency Range
40~70 Hz
Power Factor
> 0.99 (full load)
Current Harmonic Distortion
< 3%
Output
Voltage
208/120Vac, 220/127Vac (3 phase, 4-wire + G)
Voltage Regulation
± 1%
Voltage Harmonic Distortion
< 3% (linear load)
Overload Capability
<105% continuous
105%~125%: 10minute
125~150%: 1minute
>150%: 0.5 second
Output Power Factor
1
Frequency
50/60 Hz ± 0.05 Hz
Battery
Battery Quantity
Adjustable ± 11~13pcs (default 12 pcs)
Type
Support SMF and VRLA
Charge Current (Max.)
10A
Charge Voltage
Float charge 163 ± 3 Vdc
Boost charge 168 ± 3 Vdc (default 12 pcs)
Backup Time**
[20K]: 9.5 min (9Ah*48pcs)
[30K]: 9.5 min (9Ah*72pcs)
[40K]: 6.5 min (9Ah*72pcs)
[60K]: 5.2 min (9Ah*96pcs)
Communication Interfaces
SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2, Output Dry Contact x 6
Display
LED indicators and Multi-language LCD display
Conformance
Safety
UL, cUL, Energy Star
Other Features
Parallel Redundancy
Up to 4 units
Emergency Power Off
Local and remote
Efficiency
AC-AC Mode
Up to 94%
ECO Mode
Up to 98%
Environment
Operating Temperature
0 ~ 40°C
Ambient Storage Temperature
-20 ~ 40°C
Relative Humidity
0% ~ 95% (non-condensing)
Audible Noise
[20K]: < 65 dBA
[30K]: < 65 dBA
[40K]: < 70 dBA
[60K]: < 70 dBA
Physical
Dimensions (W x D x H)
[20K]: 520 x 800 x 1380 mm
[30K]: 520 x 800 x 1380 mm
[40K]: 520 x 800 x 1760 mm
[60K]: 520 x 800 x 1760 mm
Weight (with battery)
[20K]: 340 kg
[30K]: 420 kg
[40K]: 450 kg
[60K]: 530 kg
Weight (without battery)
[20K]: 196 kg
[30K]: 204 kg
[40K]: 224 kg
[60K]: 242 kg
HPH-20K-LV-B: UPS integrated battery model has batteries inside
HPH-20K-LV-BN: UPS integrated battery model has no batteries inside
HPH-20K-LV-BN: UPS integrated battery model has no batteries inside
* When input voltage range is 72~108Vac(L-N) and 125~187Vac(L-L), the sustainable loading is from 63% to 100% of UPS capacity.
** At 70% load with internal battery strings.
All specifications are subject to change without prior notice.