HPH Gen2 Series UPS, Three Phase, 20/30/40 kVA
Technical Specifications
Model
HPH-20K / HPH-30K / HPH-40K
Power Rating
● HPH-20K
20 kVA/kW
● HPH-30K
30 kVA/kW
● HPH-40K
40 kVA/kW
Input
Nominal Voltage
220/380 V, 230/400 V, 240/415 V (3-phase, 4-wire + G)
Voltage Range
305-478 Vac (full load), 228-305 Vac (with derating to 70-100%)
Current Harmonic Distortion
≤ 2%(1)
Power Factor
> 0.99
Frequency Range
40~70 Hz
Output
Voltage
220/380 V, 230/400 V, 240/415 V (3-phase, 4-wire + G)
Voltage Harmonic Distortion
≤ 1.5% (linear load)
≤ 4% (non-linear load)
Voltage Regulation
± 1% (static)
Frequency
50/60 Hz
Overload Capability
≤ 105%: continues, > 105-≤ 110%: 60 mins, > 110-≤ 125%: 10 mins
> 125-≤ 150%: 1 min, > 150%: 1 sec
Display
5” color touch screen
Interface
Standard
External battery temperature dry contact x1, Output dry contact x4, Input dry contact x2, Parallel port x2, USB Port x1, RS232 Port x1, REPO Port x1, Mini Slot x2
Conformance
Safety
CE, RCM (IEC62040-1, IEC62040-2 Class C2)
Efficiency
AC-AC Mode
> 96% (Peak efficiency)
ECO Mode
99%
Battery
Nominal Voltage
± 240 Vdc (default, ± 180(2) - ± 276 Vdc configurable)
Charge Voltage
± 272 Vdc (adjustable from 204 V to 312 V)
Maximum Inbuilt Charger Current
15 A
Environment
Operating Temperature
0 to 40℃
Relative Humidity
0-95% (non-condensing)
Audible Noise (at one meter)
< 60 dBA
IP Protection
IP20 (Standard)
Others
Parallel Redundancy and Expansion
Up to 4 units
Battery Start
Yes
Physical
Dimensions (W x D x H)
240 x 630 x 650 mm
Weight
● HPH-20K
44 kg
● HPH-30K/40K
50 kg
(1) When input voltage total harmonic distortion input is less than 1%
(2) 30-34 pcs required load derating
(2) 30-34 pcs required load derating
All specifications are subject to change without prior notice.
Options
- Battery temperature compensation cable
- Dust filter
- IP42 kit
- EPO button kit
- SNMP IPv6 card
- Modbus card
- Relay I/O card
Request A Quote |