Power Distribution Unit
Technical Specifications
Capacity
225–1000 kVA
Input
Rated Voltage
480 V (Optional: 600 V)
Connection
3-Phase 3-Wire + Ground
Frequency
50/60 Hz
Breaker
Optional
Output
Rated Voltage
415/240 V or 208/120 V
Connection
3-Phase 4-Wire + Ground
Frequency
50/60 Hz
Neutral Rating
100% (Optional: 200%)
Sub-Feed Breaker
250/400/600 A
Mounting Type
Fixed or Plug-in
Transformer
Rating
K-4 (Optional K-9, K-13, K-20)
Efficiency
DOE 2016 Compliant
Display
10” Color Touch Screen
Metered Values
Input
Phase voltage, line voltage, phase current, line current, load(%), iTHD, total kVA, total kW, total kWh, Over voltage/over current alarm, under-voltage/ under current alarm, Over line current alarm, iTHD abnormal alarm
Total Output
Phase voltage, line voltage, phase current, line current, frequency, neutral current, load(%), kVA, kW, kWh, power factor, VTHD, iTHD, Over voltage/over current alarm, under-voltage/under current alarm, Over line current alarm, iTHD abnormal alarm, VTHD abnormal alarm, power factor abnormal alarm
Output Shunt Plate
Phase current, kVA, kW, kWh, load (%), iTHD, power factor, line current, over current alarm, under current alarm, Over line current alarm, iTHD abnormal alarm, power factor abnormal alarm
Output Shunt
Current, load (%), over current alarm, under current alarm
Temperature
Environment (instant and alarm), transformers (two stage-alarm)
Communication
Protocol
Modbus RTU, Modbus TCP/IP, SNMP, Ethernet
Dry Contact
Input dray contact x 14, Output dry contact x 6
Compliance
Safety
UL891
FCC
FCC Part 15, Class A
Seismic
GR63 Zone4
Environment
Storage Temperature
-20 to 70°C (-4 to 158°F)
Operating Temperature
0 to 40°C (32 to 104°F)
Relative Humidity
0 to 95%, Noncondensing
Altitude
< 2000 m (6600 feet)
Please contact Delta personnel for further information or customized requirements of your application.