DPH Series, Three Phase, 20-80/ 50-200 kVA (FR)
Technical Specifications
Model
DPH-80K-FR / DPH-200K-FR
Power Rating
● DPH-80K-FR
20/ 40/ 60/ 80 kVA
20/ 40/ 60/ 80 kW
Frame size: 80 kW
● DPH-200K-FR
50/ 100/ 150/ 200/ 200+50 (as redundant) kVA
50/ 100/ 150/ 200/ 200+50 (as redundant) kW
Frame size: 200 kW
Parallel Configuration
Up to 8 units
Input
Nominal Voltage
380/ 400/ 415 Vac, 3P4W+PE
Voltage Range
176-276/ 305-477 Vac (full load)
132-176/ 229-305 Vac (de-rated 70% load)
Frequency
40-70 Hz
Total Harmonic Distortion (THDi)
< 3%
Power Factor
> 0.99 (full load)
Output
Nominal Voltage
380/ 400/ 415 Vac, 3P4W+PE
Voltage Regulation
±1% (static)
Frequency
50/60 ± 0.05 Hz
Total Harmonic Distortion (THDv)
≤ 1% (linear load), ≤ 4% (non-linear load)(1)
Power Factor
1.0
Overload Capability
≤ 125%: 10 minutes
≤ 150%: 1 minute
> 150%: 1 sec
Current Crest Ratio
3:1
Efficiency
Online Mode
Up to 96.5%
ECO Mode
Up to 99%
Battery
Battery Type
VRLA/ Vented lead-acid/ Lithium-ion battery
Nominal Voltage
±240 Vdc
Quantity
● DPH-80K-FR
40 pcs
● DPH-200K-FR
30(2)-46 pcs (configurable)
Maximum Charge Current
● DPH-80K-FR
32 A
● DPH-200K-FR
75 A
Internal Battery
● DPH-80K-FR
Optional, up to 5 strings
● DPH-200K-FR
N/A
External Battery Cabinet (Optional)
Parallel to 4 cabinets(3)
Communication Interface
Display
10″ color touch screen
Port
Modbus (RS-485) port, REPO, EMS/Console (RJ45), BMS (RS-485), Ethernet port x1, Input dry contact x4, Output dry contact x6, External battery temperature detection x4, External switch/breaker status dry contact x4
Protocols
SNMP, Modbus RTU, Modbus TCP/IP, HTTP(S), SNTP, SMTP, Syslog, BOOTP, DHCP
Physical
Dimensions (W x D x H)
600 x 1109 x 2000 mm
Net Weight
- UPS System
● DPH-80K-FR
269 kg
● DPH-200K-FR
275 kg
- Per Power Module
● DPH-80K-FR
18 kg
● DPH-200K-FR
36.9 kg
- Per Battery Module(3)
32.6 kg
Environment
Operating Temperature
0 to 40°C
Humidity
0-95% (non-condensing)
Altitude
0-1,000 m
Storage Temperature
-20 to +70°C
Ingress Protection
IP20
Conformance
Safety
CE, BSMI, RCM
EMC
IEC 62040-2
Performance
IEC 62040-3
Sustainability
RoHS, REACH
Features
Burn-in Test without Load Bank
Standard
Cold Start Function
Standard
Frequency Conversion
Standard
Failure Prediction
Standard
Software Integration with Delta Lithium Battery BMS
Standard
(1) Conditional
(2) 30-34 pcs require load derating
(3) Up to 10 battery strings per cabinet, featuring 40 pcs x12V 9Ah VRLA batteries each; 4 battery modules compose 1 string
(2) 30-34 pcs require load derating
(3) Up to 10 battery strings per cabinet, featuring 40 pcs x12V 9Ah VRLA batteries each; 4 battery modules compose 1 string
All specifications are subject to change without prior notice.