N Gen3 Series UPS, Single Phase, 1/2/3 kVA
Technical Specifications
Model
NX-1K / NX-2K / NX-3K
Topology
Online Double-conversion
Power Rating
● NX-1K
1 kVA / 0.9 kW
● NX-2K
2 kVA / 1.8 kW
● NX-3K
3 kVA / 2.7 kW
Input
Nominal Voltage
220/ 230 Vac, 1P2W+PE
Voltage Range
180-285 Vac (100% load)
Frequency
40-70 Hz
Power Factor
> 0.99 (100% load)
Connection
● NX-1/2K
IEC C14
● NX-3K
IEC C20
Output
Nominal Voltage
208(1)/ 220/ 230/ 240 Vac, 1P2W+PE
Voltage Regulation
±1%
Frequency
50/60 ± 3 Hz
Total Harmonic Distortion (THDv)
≤ 3% (linear load)
Power Factor
0.9
Connection
● NX-1/2K
BR Socket x4
● NX-3K
BR Socket x4 + Terminal
Overload Capability
≤ 105%: continuous
106-110%: 10 mins.
111-130%: 30 secs
131-150%: 3 secs
> 150%: immediately
Current Crest Ratio
3:1
Efficiency
Online Mode
Up to 90%
ECO Mode
Up to 95%
Battery
Battery Type
VRLA
Nominal Voltage
● NX-1K
24 Vdc
● NX-2K
48 Vdc
● NX-3K
72 Vdc
Quantity
● NX-1K
2 pcs
● NX-2K
4 pcs
● NX-3K
6 pcs
Runtime - 100% load
● NX-1K
3.1 mins
● NX-2K
3.3 mins
● NX-3K
3.6 mins
Runtime - 70% load
● NX-1K
6.1 mins
● NX-2K
6.5 mins
● NX-3K
6.9 mins
Charge Current
1 A
Communication Interface
Display
LCD screen with LED indicators
Port
USB, RS-232, mini slot (option for mini SNMP, mini Modbus and mini relay I/O card)
Audible Alarm
Battery mode, Low battery, Overload, Fault, Bypass mode
Physical
Dimensions (W x D x H)
● NX-1K
145 x 282 x 220 mm
● NX-2K
145 x 492 x 220 mm
● NX-3K
190 x 421 x 318 mm
Net Weight
● NX-1K
9.2 kg
● NX-2K
16.8 kg
● NX-3K
27 kg
Packing Dimensions (W x D x H)
● NX-1K
230 x 360 x 325 mm
● NX-2K
230 x 590 x 355 mm
● NX-3K
320 x 560 x 460 mm
Packing Weight
● NX-1K
10.3 kg
● NX-2K
18.6 kg
● NX-3K
28.4 kg
Environment
Operating Temperature
0 to 50 °C (40 to 50 °C de-rating to 70% load)
Humidity
20-90% (non-condensing)
Audible Noise(2)
< 45 dBA
Altitude
0-4,000 m (derating 1%/100m from 1,000-4,000m
Storage Temperature
-20 to 50 °C
Ingress Protection
IP20
Conformance
Safety
CE IEC 62040-1
EMC
IEC 62040-2
Sustainability
RoHS, REACH
(1) De-rating to 70% load
(2) Audible noise test with UPS < 75% load at 25°C in online mode